The battery setpoint figure read a flat zero even while the plant dispatched up to 10 MW. The setpoint figure now matches the plant's dispatch level. Plants receive this with their next agent update.
A battery converter stopped by a protection previously read as unknown, counted as available, and raised no alarm. Its operating state now reads as stopped, its own fault alarm opens five minutes after the stop, and the plant's summary alarm opens fifteen minutes after the stop. Plants receive this with their next agent update.
Linyang battery containers previously showed six temperature readings that no sensor takes, and modules 3 and 4 showed no temperature at all. Those readings have been removed, and cell temperatures are now filed under the right module.