A Zebotec PVPC park controller now shows the plant's active-power setpoints — the limit from the grid operator, the limit from the direct marketer, and the one the controller is acting on — each in percent of the plant's nameplate power. Plants receive this with their next agent update.
A Wattkraft Parkcontrol park controller is now read from its address alone, without a login, delivering the active-power setpoints of the grid operator and the direct marketer, which of them is in force, and whether the link to the direct marketer is up.
For each curtailment measure by the direct marketer, the lost energy is now recorded as a "Marketer settlement" event on the plant's "Activity" page, beside the "Redispatch settlement" events of grid-operator curtailments. The measure's own day can serve as its reference day, since only grid-operator curtailments disqualify a day. Plants receive this with their next agent update.
For each grid-operator curtailment of a solar plant, the lost energy is now worked out under the binding BilAReM method and recorded as a "Redispatch settlement" event on the plant's "Activity" page, with the reference day chosen and the lost energy per irradiation source. Plants receive this with their next agent update.
Curtailment losses are now calculated separately from the irradiation sensor, from satellite data and from weather data, with a live preview that follows a curtailment within minutes. A flat-rate method (Pauschalbilanzierung), the third German Redispatch 2.0 accounting method, holds the grid power measured before the curtailment as its reference. Plants receive this with their next agent update.