Skip to content

Changelog

Every change to Mirox, grouped by month. Filter by group or by kind of change.

Clear filters

October 20262

AgentFixMajorBattery storage

Battery setpoint no longer reads a flat zero

The battery setpoint figure read a flat zero even while the plant dispatched up to 10 MW. The setpoint figure now matches the plant's dispatch level. Plants receive this with their next agent update.

mirox-agents 3.2.175 – 3.2.176
AgentFixMajorBattery storage

Battery converter's stopped state and fault alarm now read correctly

A battery converter stopped by a protection previously read as unknown, counted as available, and raised no alarm. Its operating state now reads as stopped, its own fault alarm opens five minutes after the stop, and the plant's summary alarm opens fifteen minutes after the stop. Plants receive this with their next agent update.

mirox-agents 3.2.175 – 3.2.176

September 20262

AgentImprovements and fixesBattery storage

The direct marketer's battery setpoint is read from one more plant controller layout. A battery converter's voltages now read in volts, and the first data collection cycle at a battery plant finishes in seconds.

  • A battery storage power converter that reports voltages with no declared unit now reads them in volts.
  • The first data collection cycle at a battery plant no longer reads the cell tabs, so it finishes in seconds instead of a minute.
mirox-agents 3.2.128 – 3.2.130
AgentFeatureMajorBattery storage

A battery storage can now be added as a data logger

A battery storage can now be added as a data logger, and its converters, battery skids, and racks are then read with power, charge and discharge limits, state of charge, and the grid operator's limits on both charging and feed-in. Plants receive this with their next agent update.

mirox-agents 3.2.53 – 3.2.66mirox 2.15.457 – 2.15.467
Read more in the documentationData loggers

August 20261

AgentFeatureMajorBattery storage

A FREQCON BESS FQ battery storage system can now be added as a logger

A FREQCON BESS FQ battery storage system can now be added to a plant as a data logger, and each cabinet's state of charge, DC power, charge and discharge energy, and cell voltages and temperatures are then read. Plants receive this with their next agent update.

mirox-agents 3.1.298 – 3.1.304mirox 2.15.214 – 2.15.224
Read more in the documentationData loggers